– 94 –



61439-1 © IEC:2009



Annex E

(informative)

Rated diversity factor



E.1



General



All circuits within an ASSEMBLY are individually capable of carrying their rated current, in

accordance with 5.3.2, continuously but, the current carrying capacity of any circuit may be

influenced by adjacent circuits. Thermal interaction can result in heat being imported from, or

exported to, circuits in close proximity. Cooling air available to a circuit may be at a

temperature well in excess of the ambient due to the influence of other circuits.

In practise, not all circuits within an ASSEMBLY are normally required to carry rated current

continuously and simultaneously. Within a typical application the type and nature of loads

differ appreciably. Some circuits will be rated on the basis of inrush currents and intermittent

or short duration loads. A number of circuits may be heavily loaded while others are lightly

loaded or switched off.

To provide ASSEMBLIES in which all circuits can be operated at rated current continuously is

therefore unnecessary and would be an inefficient use of materials and resources. This

standard recognises the practical requirements of ASSEMBLIES through the assignment of a

rated diversity factor as defined in 3.8.10.

By stating a rated diversity factor, the ASSEMBLY manufacturer is specifying the ‘average’

loading conditions for which the ASSEMBLY is designed. The rated diversity factor confirms the

per unit value of rated current to which all the outgoing circuits, or a group of outgoing

circuits, within the ASSEMBLY, can be continuously and simultaneously loaded. In ASSEMBLIES

where the total of the rated currents of the outgoing circuits operating at rated diversity factor

exceeds the capacity of the incoming circuit, the diversity factor applies to any combination of

outgoing circuits used to distribute the incoming current.



E.2



Rated diversity factor of an ASSEMBLY



The rated diversity factor of an ASSEMBLY is specified in 5.3.3. For the typical ASSEMBLY shown

in Figure E.1, examples of the multitude of loading arrangements for a diversity factor of 0,8

are given in Table E.1 and shown in Figures E.2 to E.5.



E.3



Rated diversity factor of a group of outgoing circuits



In addition to stating the rated diversity factor for a complete ASSEMBLY, an ASSEMBLY

manufacturer may specify a different diversity factor for a group of related circuits within an

ASSEMBLY. Subclause 5.3.3 specifies the rated diversity factor for a group of outgoing circuits.

Tables E.2 and E.3 give examples of a diversity factor of 0,9 for a section and subdistribution

board within the typical ASSEMBLY shown in Figure E.1.



61439-1 © IEC:2009



– 95 –



D1 400 A

B1 800 A



C1 630 A



D2

A1 1600 A

Incoming

C2 200 A

B2 400 A

C3 200 A



D

2

a



D

2

b



D

2

c



D

2

d



C4 200 A

B3 400 A

C5 200 A



Section A



Section B



Section C



D2a to D2d

Each 100 A



Section D

IEC



Functional unit – Rated current (I n ) shown a

a



The rated current of the functional unit (the circuit) in the ASSEMBLY may be less than the rated current of the

device.



Figure E.1 – Typical ASSEMBLY



2046/08



b



a



1600



1600



1600



Example 3

Fig. E.4



Example 4

Fig. E.5



1600



1600



Example 2

Fig. E.3



b



A1



0



0



0



a



456



0



320



400



B2



640



640



800



B1



0



0



0



320



400



B3



504



504



504



0



630



C1



a



160



160



136



160



200



C2



C4



160



160



0



160



200



136



a



160



0



0



200



Current (A)



C3



0



160



0



0



200



C5



Balance current to load incoming circuit to its rated current.

The rated current of the functional unit (the circuit) in the ASSEMBLY may be less than the rated current of the device.



Functional unit

loading for an

ASSEMBLY with a

rated diversity

factor of 0,8



Example 1

Fig. E.2



Functional unit - rated current (In)

(See Figure E.1)



Functional unit



320



0



320



0



400



D1



80



0



0



0



100



D2a



Table E.1 – Examples of loading for an ASSEMBLY with a rated diversity factor of 0,8



80



0



0



0



100



D2b



80



0



0



0



100



D2c



80



0



0



0



100



D2d



– 96 –

61439-1 © IEC:2009



61439-1 © IEC:2009



– 97 –



[1600 A]



[320 A]

[1280 A]



B1 800 A

[640 A]



[0 A]

[320 A]



[0 A]

[0 A]

D1

400 A

[0 A]



C1 630A

[0 A]



D2

A1

1600 A

[1600 A]



Incoming

B2 400 A

[320 A]



C2 200 A

[160 A]

C3 200 A

[160 A]



B3 400 A

[320 A]



Section A



Section B



D

2

a



D

2

b



D

2

c



D

2

d



C4 200 A

[0 A]

C5 200 A

[0 A]



Section C



D2a to D2d

Each 100 A [0 A]



Section D

IEC



Actual loading is indicated by the figures in brackets e.g. [640 A].

Busbar section loading is indicated by the figure in brackets e.g. [320 A].

Figure E.2 – Example 1: Table E.1 – Functional unit loading for an ASSEMBLY

with a rated diversity factor of 0,8



2047/08