FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition

FX3U-4DA-ADP (4-channel Analog Output)



5 Changing of Output Characteristics

5.1 Example: Changing of Voltage Output Characteristics



3. Example of program 2 (For FX3S/FX3G/FX3GC Series PLC)

For example, create the following program to change the digital output data (D100) of the 1st analog special

adapter.

M8001

Normally

OFF



FNC230

LD>=

M10



D100



K0



FNC237

AND<=

FNC 22

MUL



D100 K10000



Sets the output mode of channel 1 to the

voltage output mode.



M8284



Sets the output holding function for

channel 1.



M10



D100



K1600



D101



FNC 23 D101

DDIV



K10000



D103



FNC 20 D103

ADD



K400



D107



D107



D8280



FNC 12

MOV



F-28



M8280



Check to make sure the digital

value (D100) is in range.



Calculation for changing output

characteristics.

Stores the operation result in D8280.



FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition

FX3U-4DA-ADP (4-channel Analog Output)



6 Troubleshooting

6.1 PLC Version Number Check



A

Common Items



6.



Troubleshooting



B

FX3U-4AD

FX3UC-4AD



This chapter describes the troubleshooting methods and error status.

If analog data is not output, or if the proper analog value is not output, check the following items:

• Version number of PLC

• Wiring

• Special devices



C



• Programs



6.1



FX3U-4AD-ADP



• Error status



PLC Version Number Check

• Any versions (from Ver. 1.00 (initial version) to the latest version) of the FX3S Series are compatible.

• Any versions (from Ver. 1.40 (initial version) to the latest version) of the FX3GC Series are compatible.

• Any versions (from Ver. 2.20 (initial version) to the latest version) of the FX3U Series are compatible.



6.2



Wiring Check

Check the following items for wiring:



F



The 4DA-ADP needs driving power. Verify that the power supply line is properly connected. Also check that

the POWER indicator lamp of the 4DA-ADP is on.



2. Analog output line



Special Device Check



G

FX3G-1DA-BD



Use the 2-core twisted shielded pair cable for the analog output line. In addition, be sure to separate the

analog output line from other power lines or inductive lines.

→ For a detailed description of wiring, refer to Chapter 3.



FX3U-4DA-ADP



1. Power



6.3



E

FX3U-4DA



• Check the version number of FX3UC Series. The version number should be 1.20 or later.

→ For a detailed description of the version check method,

refer to A. Common Items Subsection 5.1.2.



D

FX3G-2AD-BD



• Any versions (from Ver. 1.00 (initial version) to the latest version) of the FX3G Series are compatible.



H



Check whether the special devices for the 4DA-ADP are being used correctly:

Verify that the special device for switching the output mode is correctly set.

Turn off the device to set the output mode to the voltage output mode. Turn on the device to set the output

mode to the current output mode.



FX3U-3A-ADP



1. Output mode switching



I



2. Output setting data



3. Error status



F-29



J

FX3U-4AD-PTW

-ADP



Check that no error is detected in the 4DA-ADP.

If an error is detected, check the details of the error, and then check the wiring and programs.

→ For a detailed description of special devices, refer to Chapter 4.



FX3U-4AD-PT

-ADP



Check that the special device of the selected channel is correctly selected. This special device should be

selected depending on the connected position and the channel.



FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition



6 Troubleshooting



FX3U-4DA-ADP (4-channel Analog Output)



6.4



6.4 Program Check



Program Check

Check the following items for the program:



1. Device for setting specified digital value

Check that different values are not written to this device using other programs.



6.5



Error Status Check

If an error occurs in the 4DA-ADP, the corresponding bit will turn on.

The bit which is turned ON due to the error status is held ON until overwritten to OFF by the program or the

power is cycled.

Bit

b0



Channel-1 output data setting error



b1



Channel-2 output data setting error



b2



Channel-3 output data setting error



b3



Channel-4 output data setting error



b4



EEPROM error



b5



Unused



b6



4DA-ADP hardware error (Power supply error included)*1



b7 to b15



*1.



Description



Unused



The 4DA-ADP is supported from June, 2009 and later.

For using the 4DA-ADP, it is necessary to use a main unit whose version supports this function.

For the applicability of each combination of 4DA-ADP and main unit, refer to the table below.

4DA-ADP

FX3S

year and month

Series PLC

of production



FX3G Series PLC

Former than

Ver. 1.10



Ver. 1.20

or later



FX3GC

Series PLC



FX3U/FX3UC Series PLC

Former than

Ver. 2.60



Ver. 2.61 or

later



Former than

2009 May



Not

applicable



Not

applicable



Not

applicable



Not

applicable



Not

applicable



Not

applicable



2009 June

or later



Applicable



Not

applicable



Applicable



Applicable



Not

applicable



Applicable



For confirmation of the version of the main unit and checking the 4DA-ADP serial number, refer to the

following.

→ For details of confirmation of the PLC main unit version,

refer to A. Common Items Subsection 5.1.2.

→ For details of check of the 4DA-ADP serial number,

refer to A. Common Items Subsection 5.2.1.

To solve the problem, refer to the troubleshooting method described below:



1. Output data setting error (b0 to b3)

1) Description of error

The specified digital value is outside the specified range.

Analog data will not be correctly output.

2) Remedy

Check that the specified digital value is within the specified range.



2. EEPROM error (b4)

1) Description of error

The adjustment data set in the EEPROM before delivery from our factory cannot be read out properly or

is destroyed.

2) Remedy

Please contact your local Mitsubishi Electric representative.



F-30



FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition

FX3U-4DA-ADP (4-channel Analog Output)



6 Troubleshooting

6.5 Error Status Check



A



1) Description of error

The 4DA-ADP is not operating properly.



B

FX3U-4AD

FX3UC-4AD



2) Remedy

Check that the 24 V DC power is properly supplied to the 4DA-ADP. Also check that the 4DA-ADP is

correctly connected to the PLC.

If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric

representative.



Common Items



3. 4DA-ADP hardware error (b6)



C

FX3U-4AD-ADP



D

FX3G-2AD-BD



E

FX3U-4DA



F

FX3U-4DA-ADP



G

FX3G-1DA-BD



H

FX3U-3A-ADP



I

FX3U-4AD-PT

-ADP



J

FX3U-4AD-PTW

-ADP



F-31



FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition

FX3U-4DA-ADP (4-channel Analog Output)



MEMO



F-32



6 Troubleshooting

6.5 Error Status Check



FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition

FX3G-1DA-BD (1-channel Analog Output)



A

Common Items



B

FX3U-4AD

FX3UC-4AD



FX3S/FX3G/FX3GC/FX3U/FX3UC Series

Programmable Controllers



C

FX3U-4AD-ADP



User's Manual [Analog Control Edition]



G. FX3G-1DA-BD (1-channel Analog Output)



D

FX3G-2AD-BD



E

FX3U-4DA



F

FX3U-4DA-ADP



G

FX3G-1DA-BD



H



© 2005 MITSUBISHI ELECTRIC CORPORATION



G-1



J

FX3U-4AD-PTW

-ADP



This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent

licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property

rights which may occur as a result of using the contents noted in this manual.



I

FX3U-4AD-PT

-ADP



This manual describes the specifications, wiring, and operation method for the FX3G-1DA-BD analog output

expansion board (1-channel analog output) and should be read and understood before attempting to install or

use the unit.

Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward

it to the end user.



FX3U-3A-ADP



Foreword



FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition

FX3G-1DA-BD (1-channel Analog Output)



G-2