Tải bản đầy đủ
10 Time and time synchronisation model

10 Time and time synchronisation model

Tải bản đầy đủ

7SR210 & 7SR220 IEC 61850 Manual PIXIT, PICS, TICS

1.11 File transfer model
ID

ED

Description

Value / Clarification

Ft1

1

What is structure of files and directories?
Where are the COMTRADE files stored?
Are COMTRADE Files zipped and what files
are included in each zip file?

Directory name / COMTRADE / *;
Files according to the comtrade standard and
not zipped.

Ft2

1, 2

Directory names are separated from the file
name by

“/”

Ft3

1

The maximum file name size including path
(default 64 chars)

64

Ft4

1, 2

Are directory/file name case sensitive

Case sensitive

Ft5

1, 2

Maximum file size for SetFile

SetFile is not supported

Ft6

1

Is the requested file path included in the file
name of the MMS fileDirectory respond?

Y

Ft7

1

Is the wild char supported MMS fileDirectory
request?

Y only as *; not as name completion wild card

Ft8

1, 2

Is it allowed that 2 clients get a file at the
same time?

N

additional items:

Page 20 of 120

Maximum number of clients that can use the
File transfer service simultaneously

1

Maximum number of files that can be accessed simultaneously

1

Maximum time the file transfer service is
locked for one client

10 min

 2016, Siemens Protection Devices Ltd

7SR210 & 7SR220 IEC 61850 Manual PIXIT, PICS, TICS

1.12 General items
Description
additional items:
GOOSE Proxy object

What is the behaviour of the Device by
GetAllDataValues?

©2016 Siemens Protection Devices Limited

Value / Clarification
To be able to subscribe Data over GOOSE, Proxy
Objects are added into the object directory. Typically,
they are Data of GGIO logical nodes: SPCSOxx,
DPCSOxx. The Data Attributes of those Data are
ctlVal, q and t. The control model associated to those
Data is status-only. They are not controllable from an
IEC61850 client, and their function is only to enable the
GOOSE subscribing.
GetAllDataValues is not supported without functional
constraint indication.

Page 21 of 120

7SR210 & 7SR220 IEC 61850 Manual PIXIT, PICS, TICS

1.13 TICS - Technical Issues Implementation Conformance Statement
1.13.1 TISSUES Edition 1
The following Edition 2 TISSUES have been implemented in the device and are active within the name space
of IEC 61850-7-4:2007.

Topic
Object
Directory

Object
Model

Services

Page 22 of 120

TISSUE
No.

Link

Description

Impact of
Interoper.

433

http://tissue.iec61850.com/tissue.mspx? Order of attributes in speissueid=433
cialized CDCs for control
service mapping

-

422

http://tissue.iec61850.com/tissue.mspx? Order of extension data
issueid=422
objects and data attributes

-

168

http://tissue.iec61850.com/tissue.mspx? Order of attributes in
issueid=168
MMS components

-

141

http://tissue.iec61850.com/tissue.mspx? Desc: object reference
issueid=141
length extended to 129

x 1)

120

http://tissue.iec61850.com/tissue.mspx? Type - Mod.stVal and
issueid=120
Mod.ctlVal

-

146

http://tissue.iec61850.com/tissue.mspx? CtxInt
issueid=146

-

173

http://tissue.iec61850.com/tissue.mspx? Ctl modelling harmonizaissueid=173
tion

-

234

http://tissue.iec61850.com/tissue.mspx? New type CtxInt
issueid=234

x

75

http://tissue.iec61850.com/tissue.mspx? Desc: Str and Op Data
issueid=75
Object in GAPC

-

377

http://tissue.iec61850.com/tissue.mspx? DeleteDataSet responseissueid=377

-

276

http://tissue.iec61850.com/tissue.mspx? File Services Negative
issueid=276
Responses

-

183

http://tissue.iec61850.com/tissue.mspx? GetNameList error hanissueid=183
dling

x

165

http://tissue.iec61850.com/tissue.mspx? Improper Error Response
issueid=165
for GetDataSetValues

x

116

http://tissue.iec61850.com/tissue.mspx? GetNameList with empty
issueid=116
response?

x

 2016, Siemens Protection Devices Ltd

7SR210 & 7SR220 IEC 61850 Manual PIXIT, PICS, TICS

Topic
Reporting

TISSUE
No.

Link

Description

Impact of
Interoper.

474

http://tissue.iec61850.com/tissue.mspx? GI for URCB
issueid=474

-

453

http://tissue.iec61850.com/tissue.mspx? Reporting & Logging
issueid=453
model revision

x

438

http://tissue.iec61850.com/tissue.mspx? EntryTime base should
issueid=438
be GMT

-

349

http://tissue.iec61850.com/tissue.mspx? BRCB TimeOfEntry has
issueid=349
two definitions

x

348

http://tissue.iec61850.com/tissue.mspx? URCB class and report
issueid=348

x

344

http://tissue.iec61850.com/tissue.mspx? TimeOfEntry misspelled
issueid=344

-

335

http://tissue.iec61850.com/tissue.mspx? Clearing of Bufovfl
issueid=335

x

332

http://tissue.iec61850.com/tissue.mspx? Ambiguity in use of
issueid=332
trigger options

x

329

http://tissue.iec61850.com/tissue.mspx? Reporting and BufOvl
issueid=329

x

322

http://tissue.iec61850.com/tissue.mspx? Write Configuration atissueid=322
tribute of BRCBs

301

http://tissue.iec61850.com/tissue.mspx? SqNum in Buffered
issueid=301
Reports

-

300

http://tissue.iec61850.com/tissue.mspx? Attribute Resv in BRCB
issueid=300

x

298

http://tissue.iec61850.com/tissue.mspx? Type of SqNum
issueid=298

x

297

http://tissue.iec61850.com/tissue.mspx? Sequence number
issueid=297

x

278

http://tissue.iec61850.com/tissue.mspx? EntryId not valid for a
issueid=278
server

x

275

http://tissue.iec61850.com/tissue.mspx? Confusing statement on
issueid=275
GI usage

x

191

http://tissue.iec61850.com/tissue.mspx? BRCB: Integrity and buffissueid=191
ering reports

x

190

http://tissue.iec61850.com/tissue.mspx? BRCB: EntryId and Timissueid=190
eOfEntry

x

177

http://tissue.iec61850.com/tissue.mspx? Ignoring OptFlds bits for
issueid=177
URCB

-

52

http://tissue.iec61850.com/tissue.mspx? Ambiguity GOOSE
issueid=52
SqNum

x

49

http://tissue.iec61850.com/tissue.mspx? BRCB TimeOfEntry?
issueid=49

x

©2016 Siemens Protection Devices Limited

Page 23 of 120