1 LOCATIONS CONTAINING BATHS, SHOWERS OR OTHER FIXED WATER CONTAINERS

1 LOCATIONS CONTAINING BATHS, SHOWERS OR OTHER FIXED WATER CONTAINERS

Tải bản đầy đủ

171

(d)

A1

AS/NZS 3000:2000

Zone 3 shall be the area limited by —
(i)

the vertical plane external to Zone 2 and the parallel vertical
plane 2.40 m external to Zone 2; and

(ii)

the floor and the ceiling or the horizontal plane 2.5 m above the
floor, whichever is the lower.

NOTE: The zones do not extend beyond the boundaries of the room.

7.1.2.2 Other fixed water containers
The requirements for fixed water containers other than baths and showers
are based on the dimensions of the following two zones (examples are
given in Figure 7.1D):
A1

(a)

Zone 0 shall be the area of the interior of the water container.

(b)

Zone 2 shall be —

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

(i)

for individual water containers with a capacity not exceeding
45 L, the area limited by the —
(A) vertical plane 0.15 m from the internal rim of the water
container; and
(B) floor and the horizontal plane 0.4 m above the water
container; and

NOTE: Figure 7.1D(a) shows a typical double bowl sink where the capacity
of each container does not exceed 45 L.

(ii)

for water containers with a capacity exceeding 45 L, the area
limited by the —
(A) vertical plane 0.5 m from the internal rim of the water
container; and
(B) floor and the horizontal plane 1.0 m above the water
container.

A1

NOTES:
1 There are no Zones 1 and 3 associated with these water containers.
2 The zones do not extend beyond the boundaries of the room.

7.1.3 Protection against electric shock — Prohibited measures
The following measures of protection against electric shock shall be
prohibited:
(a)

Protection by means of obstacles in accordance with Clause 1.7.3.5.

(b)

Protection by placing out of reach in accordance with Clause 1.7.3.6.

7.1.4 Selection and installation of electrical equipment
7.1.4.1 Degree of protection required
Electrical equipment permitted to be installed in a classified zone shall have
at least the following degree of protection:

COPYRIGHT

AS/NZS 3000:2000

A1

A1

172

(a)

In Zone 0: IPX7.

(b)

In Zones 1 and 2: IPX5 in communal baths/showers; IPX4 in other
locations.

(c)

In Zone 3: IPX5 in communal baths/showers; no specific degree of
protection in other locations.

7.1.4.2 Socket-outlets
Socket-outlets shall not be installed within 0.3 m of the floor of a bathroom,
laundry or other similar location where the floor is likely to become wet.

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

In addition, and not withstanding the degree of protection required, the
following conditions shall apply to the installation of socket-outlets in the
classified zones:
(a)

In Zones 0 and 1 socket-outlets shall not be permitted.

(b)

In Zone 2, socket-outlets shall not be permitted unless they—
(i) are protected by a residual-current device with a maximum rated
residual current of 30 mA; and
(ii)

are enclosed in a cupboard provided that the enclosure is
maintained during the normal operation of the connected
equipment; or

(iii) have automatic switching and are incorporated in a shaver supply
unit complying with AS/NZS 3194.
(c)

In Zone 3, socket-outlets shall not be permitted unless they are —
(i) protected by a residual-current device with a maximum rated
residual current of 30 mA; or
(ii)

supplied individually as a separated circuit in accordance with
Clause 1.7.4.5; or

(iii) supplied as an SELV or PELV system in accordance with
Clause 7.7.
A1

7.1.4.3 Switches and other accessories
Switches and other accessories shall not be installed within 0.3 m of the
floor of a bathroom, laundry or other place where the floor is likely to
become wet.
In addition the following conditions shall apply to the installation of switches
and other accessories in the classified zones:
(a)

In Zone 0, switches and other accessories shall not be permitted.

(b)

In Zones 1 and 2, switches and other accessories with at least the
required degree of protection shall be permitted.

COPYRIGHT

173

AS/NZS 3000:2000

7.1.4.4 Other electrical equipment
The following shall apply to the installation of appliances, luminaires and
other electrical equipment in classified zones:
(a)

In Zone 0, electrical equipment with the required degree of protection
shall be permitted where it is —
(i)

specifically intended for use in a bath or water container; and

(ii)

supplied as an SELV or PELV system in accordance with
Clause 7.7 except that —
(A) the nominal voltage shall not exceed 12 V a.c. or 30 V
ripple-free d.c.; and
(B) the supply source shall be installed outside Zone 0.

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

A1

(b)

In Zones 1, 2 and 3, electrical equipment with at least the required
degree of protection shall be permitted.

(c)

In Zone 2, luminaires of Class II construction (double or reinforced
insulation) shall be permitted.

(d)

In Zones 1, 2 and 3, heating cable systems intended for heating the
location and embedded in the floor and protected in accordance with
Clause 4.3.8.5, shall be permitted.

7.1.4.5 Switchboards
Switchboards shall be installed in appropriate locations in accordance with
Clause 2.9.8.

COPYRIGHT

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

AS/NZS 3000:2000
174

A1

DIMENSIONS IN METRES

FIGURE 7.1A (in part) BATHS AND SHOWERS, ZONE DIMENSIONS
PART I—BATHS

COPYRIGHT

175

AS/NZS 3000:2000

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

A1

DIMENSIONS IN METRES

FIGURE 7.1A (in part) BATHS AND SHOWERS, ZONE DIMENSIONS
PART II—SHOWER WITH A BASE

COPYRIGHT

AS/NZS 3000:2000

176

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

A1

DIMENSIONS IN METRES

FIGURE 7.1A (in part) BATHS AND SHOWERS, ZONE DIMENSIONS
PART III—SHOWER WITHOUT A BASE

COPYRIGHT

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

177

COPYRIGHT

AS/NZS 3000:2000

A1

DIMENSIONS IN METRES

FIGURE 7.1B (in part) BATHS AND SHOWERS, ZONE DIMENSIONS (PLAN)

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

AS/NZS 3000:2000
178

A1

DIMENSIONS IN METRES

FIGURE 7.1B (in part) BATHS AND SHOWERS, ZONE DIMENSIONS (PLAN)

COPYRIGHT

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

A1

179

COPYRIGHT

AS/NZS 3000:2000

DIMENSIONS IN METRES

FIGURE 7.1C BATHS AND SHOWERS, ZONE DIMENSIONS (ELEVATION)

AS/NZS 3000:2000

180

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

A1

DIMENSIONS IN METRES

FIGURE 7.1D

FIXED WATER CONTAINERS OTHER THAN BATHS AND
SHOWERS, ZONE DIMENSIONS
COPYRIGHT

181

AS/NZS 3000:2000

7.2 SWIMMING POOLS, PADDLING POOLS AND SPA POOLS OR
TUBS
7.2.1 Scope
The particular requirements of this Clause 7.2 apply to the water
containers of swimming pools, paddling pools and spa pools or tubs
and their surrounding zones where the risk of electric shock is
increased by a reduction in body resistance and contact of the body
with earth potential.
NOTE: For swimming pools for medical or large commercial use, special
requirements may be necessary.

7.2.2 Classification of zones
7.2.2.1 Swimming pools and paddling pools

Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

The requirements for swimming pools and paddling pools are based on the
dimensions of the following three zones (examples are given in
Figures 7.2A and 7.2B):
(a)

Zone 0 shall be the area of the interior of the water container.

(b)

Zone 1, except where varied by Item (c), shall be the area limited by
the —

(c)

(d)

(i)

vertical plane 2.0 m from the internal rim of the water container;
and

(ii)

floor, or surface expected to be occupied by persons, and the
horizontal plane 2.50 m above the floor or the surface.

Zone 1, for swimming pools containing diving boards, spring boards,
starting blocks or a slide, shall be the area limited by the —
(i)

vertical plane situated 1.50 m around the diving boards, spring
boards, starting blocks or slide; and

(ii)

horizontal plane 2.50 m above the highest surface expected to be
occupied by persons.

Zone 2 shall be the area limited by the —
(i)

vertical plane external to Zone 1 and a parallel vertical plane
1.50 m external to Zone 1; and

(ii)

floor, or surface expected to be occupied by persons, and the
horizontal plane 2.50 m above the floor or surface.

NOTE: The dimensions of Zones 1 and 2 may be reduced by the installation of
suitable barriers.

7.2.2.2 Spa pools or tubs
7.2.2.2.1 General
Spa pools or tubs with a water capacity not exceeding 500 L shall comply
with the requirements of Clause 7.1.